Atman Data Center Warsaw-2
Atman Data Center Warsaw-2 is one of the two largest carrier neutral data centers in Poland. The facility is located in the very business center of Warsaw (5 Konstruktorska Street). It contains the main node of Thinx Internet exchange point.
Atman DC WAW-2 meets the requirements of the Data Centre Operations Standard by EPI at the highest level (a DCOS-4 certificate).
All Atman’s colocation facilities are 100% powered by electricity from renewable sources. Companies using our services can be sure that we care for the environment together. For more information on power in our data centers, please visit Energy security.
What you gain
Security
- 7 security zones
- Long-term lease with pre-emptive right
- Location beyond the reach of natural hazards
- Full energy autonomy
- Zero trust policy
- Own fiber-optic routes
Comfort
- Two independent entrances
(one of them open 24/7) - Protected parking lot
- On-site engineers 24/7
- Handling of courier and postal mail
- Unloading ramps, freight lift
- Safes, storerooms
Potential
- 16 MW of energy capacity allocation
- 2 floors
- Carrier neutral policy
- Proximity of important facilities (LIM, business centers)
Location
Architecture | |
Data center floor space (gross) | 6,740 sq m |
Capacity of racks | 47U |
Maximum raised floor load | 1500 kg/sq m, possibility to adjust floor carrying capacity for larger loads |
Minimum raised floor void | 700 mm |
Other | Unloading ramps, freight lifts, storage rooms on request, canteen |
Connectivity | |
External cabling | Diverse & redundant fiber-optic cabling via ducts entering the buildings from different sides |
Internal cabling | Any structured cabling on request |
Carriers and Internet exchange points | Telecommunications service from any supplier |
Power supply | |
Industrial power | 16 MW (autonomous medium-voltage power lines) |
Transformers | 8 units of total power 12,800 kVA |
UPS system | 4,000 kVA static UPS |
Diesel gensets | 4 units of total power 8,600 kVA |
Power distribution | In standard: 4 × 16 A / 230 V (2 from supply A + 2 from supply B) per rack. Other circuits possible on request |
Power density | Up to 10 kW per rack. High density solutions possible on request |
Cooling and environment control | |
Air conditioning | CRACs with N+1 redundancy |
Temperature | 18-27°C |
Relative humidity | 30-70% |
Arrangement | Server rooms in hot/cold aisle configuration |
Capacity | Up to 10 kW per rack. High density solutions possible on request |
Fire protection | |
Fire detection system | Multisensor optical-temperature smoke detection and early smoke detection systems |
Fire suppression system | Gas fire extinguishing systems – Inergen |
Zones | Separate fire zones. 120-minute fire resistance |
Security systems |
CCTV system inside and outside facilities |
Zone access control system based on proximity cards |
On request customized security systems (e.g. PIN, biometrics, man-traps) |
Visitors are escorted within the buildings |
Intrusion detection system (IDS) with automatic notification of external intervention group |
Security staff monitoring the premises 24/7 |